Standards Compliance
  IEC 61643-1 class II, III
  AS/NZS 1768 categories A, B
  IEEE C62.41 categories A, B
  BS 6651 categories A, B
  CP 33 categories A, B
  IEC 1000-4-5-1995
  UL1449 third edition
 

surge protection  DINsafe - SDD1 Surge Diverters
Product Features
Compliant with the relevant IEC lightning and surge protection standards, in particular IEC 62305 and IEC 61643. All Mode Protection - Novaris models featuring all mode protection provide protection for all combinations of lines (L-N, L-E, N-E) ensuring the maximum level of protection is achieved at all times. They have been designed for installation in any wiring system worldwide. Thermal Sensing - Sustained overvoltages can cause components to overheat and degrade. LED Status Display - LED indicators are provided on models to indicate operating status. External Alarms - Models featuring external alarms have voltage free changeover contacts for remote status indication. DIN 43880 Compliant - Protection devices housed in DIN 43880 compliant enclosures allow for convenient installation on DIN rail fittings commonly used in switchboards worldwide. Safe Metal Enclosure - Novaris surge protection products are housed in safe, all metal enclosures. In the event of a prolonged overvoltage they will not catch fire or explode.
Product Description
Novaris SDD DINsafe Surge Diverters offer powerful performance at domestic MSB and industrial DBs. The SDD diverters are housed in a DIN compliant, fail-safe metal enclosure.

click here to see three phase

[ Download/View novaris_SDD1-50.pdf ]

  
    SDD1-25-   275 SDD1-50- 275 SDD1-100- 275 SDD1-100- 275-A
Electrical Specifications
Connection type Shunt
Modes of protection All mode (L-N, L-PE, N-PE)
Phases 1
Nominal voltage U0 230V / 50Hz
Maximum continuous voltage UC 275V / 50Hz
Maximum discharge current (8/20μs) I max 25kA 50kA 100kA
Voltage protection level @ 3kA (8/20μs) U p <800V
Response time tA <5ns
Earth leakage current <10μA
Display LED status
Alarms (optional) Segment / thermal failure, clean SPDT contact
Alarm isolation 4kV
Backup fuse (HRC) 32A


 
Mechanical Specifications
Operating temperature / humidity -40 to +40ºC / 0 to 90% non-condensing
Terminal capacity - power 16mm2
Terminal capacity - alarms 2.5mm2
Terminal screw torque - power 1.0Nm
Terminal screw torque - alarm 0.5Nm
Environmental IP 20
Mounting TS35 DIN rail
Enclosure / Colour Metal / black
Weight 270g 300g






Dimensions
Width 36mm 72mm
Height 95mm
Depth 80mm






Options
External alarm A Standard
Polycarbonate enclosure P
Voltage variations UC 50V / 130V 130V