PP13B2-19 |
PP13B2-50 |
PP15A1-19 |
PP15A1-50 |
| Electrical Specifications |
| Connection type |
Series |
| Modes of protection |
All mode (L-N, L-PE, N-PE) |
| Nominal voltage |
U0 |
230V / 50Hz |
| Maximum continuous voltage |
Uc |
275V / 50Hz |
| Maximum discharge current (8/20μs) |
Imax |
19kA |
50kA |
19kA |
50kA |
| Maximum load curent |
IL |
13A |
15A |
|
| Protection stages |
Metal oxide varistor / LC filter / metal oxide varistor |
| Voltage protection level @ 3kA (8/20μs) |
U p |
<360V |
| Response time |
tA |
Instantaneous |
| Earth leakage current |
<200μA |
| Maximum voltage drop (% of U0) |
ΔU |
<1% |
| Display |
LED power and status |
|
|
|
|
|
|
| Mechanical Specifications |
| Operating temperature / humidity |
-40 to +40ºC / 0 to 90% non-condensing |
| Connection type - line side cord |
UK plug |
Australian plug |
| Connection type - load side outlet |
UK socket |
Australian socket |
| Number of outlets |
2 |
1 |
| Environmental |
IP 20 |
| Mounting |
Free standing, optional wall mount |
| Weight |
1.3kg |
|
|
|
|
|
|
| Dimensions |
| Width |
170mm |
| Height |
100mm |
| Depth |
60mm |
|
|
|
|
|
|
| Options |
| Integrated two pair RJ12 protection |
C |
- |
| Integrated F-type comms. protection |
F |
- |
| Integrated RJ45 CAT6 comms. protection |
J |
- |
| Integrated RJ45 CAT6 PoE protection |
P |
- |
| Wall mounting option* |
M |
| RFI line filtering* |
R |
- |
| IEC 3 pin outlet, Australian plug |
- |
I |