Novaris
Novaris Global Solutions in Lightning and Surge Protection
site search
Novaris
lighting and surge protection
surge protection Products : Product Range : Surge Filters back-buttonrequest-quote
 

Standards Compliance
  IEC 61643-1 class I
  AS/NZS 1768 category C
  IEEE C62.41 category C
  BS 6651 category C
  CP 33 category C
  IEC 1000-4-5
  UL1449 third edition

Options
  Metal enclosure IP 55 M
  Over / under voltage relay O
  Extended voltage (95-15V) X

surge protection  SFH - 1200A & 1600A Surge Filters
Product Features
Compliant with the relevant IEC lightning and surge protection standards, in particular IEC 62305 and IEC 61643. All Mode Protection - Novaris models featuring all mode protection provide protection for all combinations of lines (L-N, L-E, N-E) ensuring the maximum level of protection is achieved at all times. They have been designed for installation in any wiring system worldwide. Multistage Transient Protection - Models featuring multistage transient protection deliver greater levels of protection through a staged approach. The primary stage absorbs the majority of the surge energy. The remaining stages provide accurate clamping and a degree of redundancy. Redundant Segments - Models featuring redundant segments have a parallel redundant arrangement of high energy metal oxide varistors (MOVs), thus promoting long life and exceptional surge handling capacity. Thermal Sensing - Sustained overvoltages can cause components to overheat and degrade. Percentage Active Display - A digital display confirms the device rating upon switch on then displays percentage active. The display indicates segment status and thermal overload. LED Status Display - LED indicators are provided on models to indicate operating status. External Alarms - Models featuring external alarms have voltage free changeover contacts for remote status indication. Safe Metal Enclosure - Novaris surge protection products are housed in safe, all metal enclosures. In the event of a prolonged overvoltage they will not catch fire or explode.
Product Description
Novaris SFH surge filters provide the highest level of protection with the lowest let through voltage.  When installed at a main switchboard Novaris surge filters will protect all connected equipment.

click here for 250A - 400A Surge filters

click here for 630A - 800A Surge filters

click here for 2000A Surge filters 

[ Download/View NovarisSFH3-1200-0708_1.pdf ]

 

  
    SFH3-1200 100-275 SFH3-1200 200-275 SFH3-1600 100-275 SFH3-1600 200-275
Electrical Specifications
 Connection type Series
 Modes of protection All mode (L-N, L-PE, N-PE)
 Nominal voltage U0 230V / 50Hz
 Maximum continuous voltage Uc 275V / 50Hz
 Phases 3
 Discharge current 8/20μs Imax 100kA 200kA 100kA 200kA
 Maximum load current IL 1200A 1600A
 Protection stages Metal oxide varistor / LC filter / metal oxide varistor
 Voltage protection @ 3kA (8/20μs) U p <360V
 Response time tA Instantaneous
 Earth leakage current <1μA
 Maximum voltage drop (% of U0) ΔU <1%
 3dB Frequency @ 50Ω 80Hz
 Displays 7-segment LED, percentage active
 Alarms Segment / thermal failure, clean SPDT contact
 Alarm isolation to active circuitry 4kV
           
Mechanical Specifications
 Operating temperature / humidity -40 to +40ºC / 0 to 90% non-condensing
 Connection type Bus bar / cable lug
 Alarm terminal capacity 2.5mm2
 Terminal screw torque 0.5Nm
 Environmental IP 55 in enclosure
 Mounting Wall mount
 Weight 120kg
           
Dimensions (in enclosure)
 Width 1325mm
 Height 914mm
 Depth 303mm
           
Maximum Discharge Current Variations
 Discharge Current variations Imax 150kA / 250kA