Standards Compliance
  IEC 61643-1 class I
  AS/NZS 1768 category C
  IEEE C62.41 category C
  BS 6651 category C
  CP 33 category C
  IEC 1000-4-5
  UL1449 third edition

Options
  Metal enclosure IP 55 M
  Over / under voltage relay O
  Extended voltage (95-15V) X

surge protection  SFH - 2000A Surge Filters
Product Features
Compliant with the relevant IEC lightning and surge protection standards, in particular IEC 62305 and IEC 61643. All Mode Protection - Novaris models featuring all mode protection provide protection for all combinations of lines (L-N, L-E, N-E) ensuring the maximum level of protection is achieved at all times. They have been designed for installation in any wiring system worldwide. Multistage Transient Protection - Models featuring multistage transient protection deliver greater levels of protection through a staged approach. The primary stage absorbs the majority of the surge energy. The remaining stages provide accurate clamping and a degree of redundancy. Redundant Segments - Models featuring redundant segments have a parallel redundant arrangement of high energy metal oxide varistors (MOVs), thus promoting long life and exceptional surge handling capacity. Thermal Sensing - Sustained overvoltages can cause components to overheat and degrade. Percentage Active Display - A digital display confirms the device rating upon switch on then displays percentage active. The display indicates segment status and thermal overload. LED Status Display - LED indicators are provided on models to indicate operating status. External Alarms - Models featuring external alarms have voltage free changeover contacts for remote status indication. Safe Metal Enclosure - Novaris surge protection products are housed in safe, all metal enclosures. In the event of a prolonged overvoltage they will not catch fire or explode.
Product Description
Novaris SFH surge filters provide the highest level of protection with the lowest let through voltage.  When installed at a main switchboard Novaris surge filters will protect all connected equipment.

click here for 250A - 400A Surge filters

click here for 630A - 800A Surge filters

click here for 1200A - 1600A Surge filters

[ Download/View NovarisSFH3-1200-0708.pdf ]

  
 

SFH3-2000-100-275

SFH3-2000-200-275

Electrical Specifications
  Connection type Series
  Modes of protection All mode (L-N, L-PE, N-PE)
  Nominal voltage U0 230V / 50Hz
  Maximum continuous voltage Uc 275V / 50Hz
  Phases 3
  Discharge current 8/20μs Imax 100kA 200kA
  Maximum load current IL 2000A
  Protection stages Metal oxide varistor / LC filter / metal oxide varistor
  Voltage protection @ 3kA (8/20μs) U p <360V
  Response time tA Instantaneous
  Earth leakage current <1μA
  Maximum voltage drop (% of U0) ΔU <1%
  3dB Frequency @ 50Ω 80Hz
  Displays 7-segment LED, percentage active
  Alarms Segment / thermal failure, clean SPDT
  Alarm isolation to active circuitry 4kV
       
Mechanical Specifications
  Operating temperature / humidity -40 to +40ºC / 0 to 90% non-condensing
  Connection type Bus bar / cable lug
  Alarm terminal capacity 2.5mm2
  Terminal screw torque 0.5Nm
  Environmental IP 55 in enclosure
  Mounting Wall mount
  Weight 120kg
       
Dimensions (in enclosure)
  Width 1325mm
  Height 914mm
  Depth 303mm
       
Maximum Discharge Current Variations
  Discharge Current variations Imax 150kA / 250kA
novaris