Novaris
Novaris Global Solutions in Lightning and Surge Protection
site search
Novaris
lighting and surge protection
surge protection Products : Product Range : Surge Filters back-buttonrequest-quote
 

  
Standards Compliance
  IEC 61643-1 class I, II
  AS/NZS 1768 categories B, C
  IEEE C62.41 categories B, C
  BS 6651 categories B, C
  CP 33 categories B, C
  IEC 1000-4-5
  UL1449 third edition


Options
  Circuit breaker C
  HRC fusing H
  Metal enclosure IP 55 M
  Over / under voltage relay O
  Extended voltage (95-415V) X

surge protection  SFM - 40A MSB & DB single phase protection
Product Features
Compliant with the relevant IEC lightning and surge protection standards, in particular IEC 62305 and IEC 61643. All Mode Protection - Novaris models featuring all mode protection provide protection for all combinations of lines (L-N, L-E, N-E) ensuring the maximum level of protection is achieved at all times. They have been designed for installation in any wiring system worldwide. Multistage Transient Protection - Models featuring multistage transient protection deliver greater levels of protection through a staged approach. The primary stage absorbs the majority of the surge energy. The remaining stages provide accurate clamping and a degree of redundancy. Redundant Segments - Models featuring redundant segments have a parallel redundant arrangement of high energy metal oxide varistors (MOVs), thus promoting long life and exceptional surge handling capacity. Thermal Sensing - Sustained overvoltages can cause components to overheat and degrade. Percentage Active Display - A digital display confirms the device rating upon switch on then displays percentage active. The display indicates segment status and thermal overload. LED Status Display - LED indicators are provided on models to indicate operating status. External Alarms - Models featuring external alarms have voltage free changeover contacts for remote status indication. Safe Metal Enclosure - Novaris surge protection products are housed in safe, all metal enclosures. In the event of a prolonged overvoltage they will not catch fire or explode.
Product Description
Novaris SFM surge filters provide excellent and effective MSB and DB protection for critical equipment up to 40A per phase.

[ Download/View NovarisSFM40-0708_1.pdf ]


SFM1-40 50-275 SFM1-40 100-275 SFM3-40 50-275 SFM3-40 100-275
Electrical Specifications
  Connection type Series
  Modes of protection All mode (L-N, L-PE, N-PE)
  Nominal Voltage U0 230V / 50Hz (110V / 60Hz by request only)
  Maximum continuous voltage Uc 275V / 50Hz (130V / 60Hz by request only)
  Phases 1 3
  Discharge current 8/20μs Imax 50kA 100kA 50kA 100kA
  Maximum load current IL 40A
  Protection stages Metal oxide varistor / LC filter / metal oxide varistor
  Voltage protection @ 3kA(8/20μs) Up <360V
  Response time tA Instantaneous
  Earth leakage current <1μA
  Maximum voltage drop (% of U0) ΔU <1%
  3dB Frequency @ 50Ω 750Hz
  Displays LED status % active LED status % active
  Alarms Segment failure and overcurrent / thermal overload, SPDT
  Alarm isolation to active circuitry 4kV






Mechanical Specifications
  Operating temperature / humidity -40 to +40ºC / 0 to 90% non-condensing
  Connection type UIK35 Terminals
  Terminal capacity - power 35mm2
  Terminal capacity - alarm 2.5mm2
  Terminal screw torque - power 1.0Nm
  Terminal screw torque - alarm 0.5Nm
  Environmental IP 55 in enclosure
  Mounting Wall mount
  Weight (in enclosure) 9kg 10kg 18kg 22kg






Dimensions (in enclosure)
  Width 310mm 426mm
  Height 390mm 506mm
  Depth 130mm 200mm






Maximum Discharge Current Variations
  Discharge Current variations Imax 150kA / 200kA / 250kA