Standards Compliance
  IEC 61643-1 class I, II
  AS/NZS 1768 categories B, C
  IEEE C62.41 categories B, C
  BS 6651 categories B, C
  CP 33 categories B, C
  IEC 1000-4-5
  UL1449 third edition


Options
  Circuit breaker C
  HRC fusing H
  Metal enclosure IP 55 M
  Over / under voltage relay O
  Extended voltage (95-415V) X

surge protection  SFM - 63A MSB & DB protection
Product Features
Compliant with the relevant IEC lightning and surge protection standards, in particular IEC 62305 and IEC 61643. All Mode Protection - Novaris models featuring all mode protection provide protection for all combinations of lines (L-N, L-E, N-E) ensuring the maximum level of protection is achieved at all times. They have been designed for installation in any wiring system worldwide. Multistage Transient Protection - Models featuring multistage transient protection deliver greater levels of protection through a staged approach. The primary stage absorbs the majority of the surge energy. The remaining stages provide accurate clamping and a degree of redundancy. Redundant Segments - Models featuring redundant segments have a parallel redundant arrangement of high energy metal oxide varistors (MOVs), thus promoting long life and exceptional surge handling capacity. Thermal Sensing - Sustained overvoltages can cause components to overheat and degrade. Percentage Active Display - A digital display confirms the device rating upon switch on then displays percentage active. The display indicates segment status and thermal overload. LED Status Display - LED indicators are provided on models to indicate operating status. External Alarms - Models featuring external alarms have voltage free changeover contacts for remote status indication. Safe Metal Enclosure - Novaris surge protection products are housed in safe, all metal enclosures. In the event of a prolonged overvoltage they will not catch fire or explode.
Product Description
Novaris SFM surge filters provide excellent and effective MSB and DB protection for critical equipment up to 63A per phase.

[ Download/View NovarisSFM40-0708.pdf ]


SFM1-63 50-275 SFM1-63 100-275 SFM3-63 50-275 SFM3-63 100-275
Electrical Specifications
Connection type Series
Modes of protection All mode (L-N, L-PE, N-PE)
Nominal Voltage U0 230V / 50Hz (110V / 60Hz by request only)
Maximum continuous voltage Uc 275V / 50Hz (130V / 60Hz by request only)
Phases 1 3
Discharge current 8/20μs Imax 50kA 100kA 50kA 100kA
Maximum load current IL 63A
Protection stages Metal oxide varistor / LC filter / metal oxide varistor
Voltage protection @ 3kA (8/20μs) Up <360V
Response time tA Instantaneous
Earth leakage current <1μA
Maximum voltage drop (% of U0) ΔU <1%
3dB Frequency @ 50Ω 750Hz
Displays LED status % active LED status % active
Alarms Segment failure and over current/thermal overload, SPDT
Alarm isolation to active circuitry 4kV






Mechanical Specifications
Operating temperature / humidity -40 to +40ºC / 0 to 90% non-condensing
Connection type UIK35 Terminals
Terminal capacity - power 35mm2
Terminal capacity - alarm 2.5mm2
Terminal screw torque - power 1.0Nm
Terminal screw torque - alarm 0.5Nm
Environmental IP 55 in enclosure
Mounting Wall mount
Weight (in enclosure) 10kg 11kg 20kg 24kg






Dimensions (in enclosure)
Width 310mm 426mm
Height 390mm 506mm
Depth 130mm 200mm






Maximum Discharge Current Variations
Discharge Current variations Imax 150kA / 200kA / 250kA