Novaris
Novaris Global Solutions in Lightning and Surge Protection
site search
Novaris
lighting and surge protection
surge protection Products : Product Range : Surge Filters back-buttonrequest-quote
 

  
Standards Compliance
  IEC 61643-1 class II, III
  AS/NZS 1768 categories A, B
  IEEE C62.41 categories A, B
  BS 6651 categories A, B
  CP 33 categories A, B
  IEC 1000-4-5
  UL1449 third edition

surge protection  Surge Filters 10A
Product Features
Compliant with the relevant IEC lightning and surge protection standards, in particular IEC 62305 and IEC 61643. All Mode Protection - Novaris models featuring all mode protection provide protection for all combinations of lines (L-N, L-E, N-E) ensuring the maximum level of protection is achieved at all times. They have been designed for installation in any wiring system worldwide. Multistage Transient Protection - Models featuring multistage transient protection deliver greater levels of protection through a staged approach. The primary stage absorbs the majority of the surge energy. The remaining stages provide accurate clamping and a degree of redundancy. LED Status Display - LED indicators are provided on models to indicate operating status. External Alarms - Models featuring external alarms have voltage free changeover contacts for remote status indication. DIN 43880 Compliant - Protection devices housed in DIN 43880 compliant enclosures allow for convenient installation on DIN rail fittings commonly used in switchboards worldwide. Safe Metal Enclosure - Novaris surge protection products are housed in safe, all metal enclosures. In the event of a prolonged overvoltage they will not catch fire or explode.
Product Description
Novaris SFD surge filters provide the highest level of protection for critical and essential equipment up to 6A per phase.

[ Download/View novaris_SFD-2-10A.pdf ]

  
    SFD1-10 13-275 SFD1-10 50-275-A SFD3-10 13-275-A SFD3-10 50-275-A
Electrical Specifications
Connection type Series
Modes of protection All mode (L-N, L-PE, N-PE)
Nominal voltage U0 230V / 50Hz
Maximum continuous voltage Uc 275V / 50Hz
Phases 1 3 1 3
Maximum discharge current (8/20μs) Imax 13kA 50kA 13kA 50kA
Maximum load curent IL 10A
Protection stages MOV / LC filter / MOV
Voltage protection level @ 3kA (8/20μs) <700V
Response time tA Instantaneous
Earth leakage current <500μA
Maximum voltage drop (% of U0) ΔU

<1%


Displays (optional) LED power and status
Alarms (optional) Overcurrent / thermal, SPDT contact
Alarm isolation to active circuitry 4kV







Mechanical Specifications          
Operating temperature / humidity -40 to +40ºC / 0 to 90% non-condensing
Terminal capacity - power 2.5mm2
Terminal capacity - alarm 2.5mm2
Terminal screw torque - power 1.0Nm
Terminal screw torque - alarm 0.5Nm
Environmental IP 20
Mounting TS35 DIN rail
Weight 450g 1.05kg 1.55kg







Dimensions
Width* (can vary with options) 54mm 118mm 180mm
Height* (can vary with options) 95mm
Depth 78mm







Options          
LED indication and external alarm - Standard
LED indication only L
Polycarbonate enclosure P
Voltage variation Uc 50V / 130V 130V 50V / 130V 130V
novaris