SFD1-2 6.5-130-C |
SFD1-6 6.5-130-C |
SFD1-2 6.5-275-C |
SFD1-6 6.5-275-C |
| Power Line Protection |
| Connection type |
Series |
| Modes of protection |
All mode (L-N, L-PE, N-PE) |
| Nominal voltage |
U0 |
110V / 50Hz |
230V / 50Hz |
| Maximum continuous voltage |
Uc |
130V / 50Hz |
275V / 50Hz |
| Phases |
1 |
| Maximum discharge current (8/20μs) |
Imax |
6.5kA |
| Maximum load current |
IL |
2A |
6A |
2A |
6A |
| Protection stages |
Metal oxide varistor / LC filter / metal oxide varistor |
| Voltage protection level @ 3kA (8/20μs)) |
UP |
<450V |
<750V |
| Response time |
tA |
Instantaneous |
| Earth leakage current |
<500uA |
| Maximum voltage drop (% of U0) |
ΔU |
<1% |
|
|
|
|
|
|
| Signal Line Protection |
| Connection type |
Series |
| Modes of protection |
Transverse and common modes |
| Maximum continuous voltage |
Uc |
8.2V |
| Maximum discharge current (8/20μs) |
Imax |
20kA |
| Maximum load current |
IL |
500mA |
| Protection stages |
Gas discharge tube / series impedance / SAD |
| Impulse voltage 1.2/50μs |
UP |
14V |
| 3dB frequency |
20MHz |
| Insertion loss |
<1dB @ 20MHz |
|
|
|
|
|
|
| Mechanical Specifications |
| Operating temperature / humidity |
-40 to +85ºC / 0 to 90% non-condensing |
| Connector type - power |
2.5mm2 polarised plugs |
| Connector type - signal |
Female / female BNC |
| Terminal screw torque |
0.5 Nm |
| Environmental |
IP 20 |
| Mounting |
TS35 DIN rail |
| Weight |
300g |
|
|
|
|
|
|
| Dimensions |
| Width |
28mm |
| Height |
116mm |
| Depth |
78mm |