Novaris
Novaris Global Solutions in Lightning and Surge Protection
site search
Novaris
lighting and surge protection
surge protection Products : Product Range : LAN & CCTV back-buttonrequest-quote
 

Standards Compliance
  IEC 61643-1 class II, III
  AS/NZS 1768 categories A, B
  IEEE C62.41 categories A, B
  BS 6651 categories A, B
  CP 33 categories A, B
  IEC 1000-4-5
  UL1449 third edition
  ITU-T K.44
  IEC 61643-21
  UL497B

surge protection  SFD Combined Power and Signal Protector 130-275 Series
Product Features
Compliant with the relevant IEC lightning and surge protection standards, in particular IEC 62305 and IEC 61643. All Mode Protection - Novaris models featuring all mode protection provide protection for all combinations of lines (L-N, L-E, N-E) ensuring the maximum level of protection is achieved at all times. They have been designed for installation in any wiring system worldwide. Multistage Transient Protection - Models featuring multistage transient protection deliver greater levels of protection through a staged approach. The primary stage absorbs the majority of the surge energy. The remaining stages provide accurate clamping and a degree of redundancy. DIN 43880 Compliant - Protection devices housed in DIN 43880 compliant enclosures allow for convenient installation on DIN rail fittings commonly used in switchboards worldwide. Safe Metal Enclosure - Novaris surge protection products are housed in safe, all metal enclosures. In the event of a prolonged overvoltage they will not catch fire or explode.
Product Description
Novaris protection for both power and signal is provided in one compact and economical DIN compliant package. Ideal for security and CCTV camera protection.

[ Download/View NovarisSFD1combined-0708_1.pdf ]

   
 
    SFD1-2 6.5-130-C SFD1-6 6.5-130-C SFD1-2 6.5-275-C SFD1-6 6.5-275-C
Power Line Protection
  Connection type Series
  Modes of protection All mode (L-N, L-PE, N-PE)
  Nominal voltage U0 110V / 50Hz 230V / 50Hz
  Maximum continuous voltage Uc 130V / 50Hz 275V / 50Hz
  Phases 1
  Maximum discharge current (8/20μs) Imax 6.5kA
  Maximum load current IL 2A 6A 2A 6A
  Protection stages Metal oxide varistor / LC filter / metal oxide varistor
  Voltage protection level @ 3kA (8/20μs)) UP <450V <750V
  Response time tA Instantaneous
  Earth leakage current <500uA
  Maximum voltage drop (% of U0) ΔU <1%






Signal Line Protection
  Connection type Series
  Modes of protection Transverse and common modes
  Maximum continuous voltage Uc 8.2V
  Maximum discharge current (8/20μs) Imax 20kA
  Maximum load current IL 500mA
  Protection stages Gas discharge tube / series impedance / SAD
  Impulse voltage 1.2/50μs UP 14V
  3dB frequency 20MHz
  Insertion loss <1dB @ 20MHz






Mechanical Specifications
  Operating temperature / humidity -40 to +85ºC / 0 to 90% non-condensing
  Connector type - power 2.5mm2 polarised plugs
  Connector type - signal Female / female BNC
  Terminal screw torque 0.5 Nm
  Environmental IP 20
  Mounting TS35 DIN rail
  Weight 300g

         
Dimensions
  Width 28mm
  Height 116mm
  Depth 78mm