surge protection Products : Product Range : Spark Gaps back-buttonrequest-quote
 

  
Standards Compliance
  IEC 61643-1 class 1
  AS/NZS 1768 category C
  IEEE C 62.41 category C
  BS 6651 category C
  CP 33 category C
  IEC 1000-4-5
  UL1449 third edition

surge protection  Hybrid Spark Gap Arresters
Product Features
Compliant with the relevant IEC lightning and surge protection standards, in particular IEC 62305 and IEC 61643. All Mode Protection - Novaris models featuring all mode protection provide protection for all combinations of lines (L-N, L-E, N-E) ensuring the maximum level of protection is achieved at all times. They have been designed for installation in any wiring system worldwide. Redundant Segments - Models featuring redundant segments have a parallel redundant arrangement of high energy metal oxide varistors (MOVs), thus promoting long life and exceptional surge handling capacity. LED Status Display - LED indicators are provided on models to indicate operating status. External Alarms - Models featuring external alarms have voltage free changeover contacts for remote status indication. Safe Metal Enclosure - Novaris surge protection products are housed in safe, all metal enclosures. In the event of a prolonged overvoltage they will not catch fire or explode.
Product Description
Novaris HSG Hybrid Spark Gap Arresters combine the best qualities of voltage switching and voltage limiting components. Novaris HSG hybrid spark gaps suit all high exposure installations. There is no follow on current.  The HSG is ideal for applications where mains voltages fluctuations are significant.

[ Download/View novaris_HSG.pdf ]

  
    HSG1-25-275 HSG3-25-275
Electrical Specifications
Connection type Shunt
Modes of protection L-N
Phases 1 3
Nominal voltage U0 230V / 50Hz
Maximum continuous voltage U c 275V / 50Hz
Interrupting follow current @ Uc Ifi -
Lightning impulse voltage sparkover (1.2/50μs) U p <1.3kV
Maximum impulse current (10/350μs) Iimp 25kA
Charge Q 12.5As
Specific energy W/R 625kJ/Ω
Response time tA <100ns
Display LED status
Alarms Clean SPDT contact
Alarm isolation to active circuitry 4kV
Backup fuse (HRC) 63A




Mechanical Specifications
Operating temperature / humidity -40 to +80ºC / 0 to 90%
Terminal capacity - power 16mm2
Terminal capacity - alarms 2.5mm2
Terminal screw torque - power 1.0Nm
Terminal screw torque - alarms 0.5Nm
Environmental IP 20
Mounting Panel mount / TS35 DIN
Enclosure / colour Metal / Blue
Weight 1.2kg 5.0kg




Dimensions
Width 60mm 240mm
Height 200mm 260mm
Depth 70mm 78mm




Options
Neutral-earth protection N
Metal enclosure M
Over / under voltage relay O